All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

12

Rockwell Automation Publication 1606-RM031A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

14. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 14-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

3.2W/°C

45-60°C (113°F to 140°F)

6W/°C

60-70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis

IEC 60068-2-6

Shock

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 6000m (0 to 20 000ft)

reduce output power or ambient temperature
above 2000m sea level.

Altitude de-rating

15W/1000m or 5°C/1000m

above 2000m (6500ft), see Fig. 14-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize in the presence of condensation.

Fig. 14-1 Output current vs. ambient temp.

Fig. 14-2 Output current vs. altitude at 48V

0

-25

0

20

40

70°C

1

2

3

4

5

6A

60

Ambient Temperature

continuous

short

term

Allowable Output
Current at 48V

0

0

2000

4000

6000m

1

2

3

4

5

6A

Altitude

A... Tamb < 60°C

B... Tamb < 50°C
C... Tamb < 40°C

C

B

A

short term

Allowable Output
Current at 48V