All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM031A-EN-P — April 2014

9

Bulletin 1606 Switched Mode Power Supplies

9. Functional Diagram

Fig. 9-1 Functional diagram

+

+

-
-

V

OUT

Output

Over-

Voltage

Protection

PFC

Inductor

Inrush

Limiter

Transient

Filter

Input Fuses

Input Filter

Input
Rectifier

Output

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

DC-ok

LED

L2
L3

L1

Single /

Parallel

10. Front Side and User Elements

A Output Terminals

Screw terminals, dual terminals per pole

+ Positive output

- Negative (return) output

B Input

Terminals

Screw

terminals

L1, L2, L3 Phase input

PE (Protective Earth) input

C Output

voltage

potentiometer

Open the flap to set the output voltage. Factory set: 48.0V

D “Parallel Use” “Single Use” selector

Set jumper to “Parallel Use” when power supplies are connected in
parallel to increase the output power. In order to achieve a sharing of
the load current between the individual power supplies, the “parallel
use” regulates the output voltage in such a manner that the voltage at
no load is approx. 5% higher than at nominal load. See also Fig. 6-2.
A missing jumper is equal to a “Single Use” mode.
Factory setting is “Single Use” mode.

E DC-OK LED (green)

On when the voltage on the output terminals is > 36V

A

B

C

D

E

Fig. 10-1 Front side