All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

4

Rockwell Automation Publication 1606-RM031A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

3. AC Input

AC input

nom.

3AC 380-480V

TN, TT, IT-mains networks,
grounding of one phase is allowed except for UL508
applications

AC input range

3x 323-576Vac

continuous operation

3x 576-700Vac

for max. 1 second, occasional (not periodical)

3x 200-323Vac

full power for 200ms, no damage between 0 and 200Vac

Allowed Voltage Phase to Earth

500Vac

IEC 62103

Input frequency

nom.

50–60Hz

±6%

Turn-on voltage

typ.

3x 260Vac

steady-state value, see Fig. 3-1

Shut-down voltage

typ.

3x 185Vac

steady-state value, see Fig. 3-1

3AC 400V

3AC 480V

Input current

typ.

0.7A

0.6A

at 48V, 5A, symmetrical phase voltage,
see Fig. 3-3

Power factor *)

typ.

0.53

0.52

at 48V, 5A, see Fig. 3-4

Start-up delay

typ.

90ms

90ms

see Fig. 3-2

Rise time

typ.

55ms

55ms

0mF, 48V, 5A, see Fig. 3-2

typ.

140ms

140ms

5mF,

48V,

5A,

see

Fig.

3-2

Turn-on overshoot

max.

300mV

300mV

see Fig. 3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

Fig. 3-1 Input voltage range

Fig. 3-2 Turn-on behavior, definitions

Turn-on

323V

Rated input

range

V

IN

P

OUT

185V

576V

Shut

-do

wn

260V

3x700Vac

< 1s

Start-up

delay

Rise

Time

Ov

ersh

oot

- 5%

Output
Voltage

Input
Voltage

Fig. 3-3 Input current vs. output load at 24V

Fig. 3-4 Power factor vs. output load

6A

0

1

3

4

0

0.1

0.2

0.4

0.5

0.6

0.8A

Input Current, typ.

Output Current

2

5

0.3

0.7

3x

48

0V

ac

3x

40

0V

ac

6A

0

1

3

4

0.35

0.40

0.45

0.50

0.55

Power Factor, typ.

Output Current

2

5

3x480Vac

3x400Vac