Parameter and variable descriptions – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 84

Advertising
background image

6-28

PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



13 Analog Output Parameters

Analog Offset 4L [Analog offset 4L]
Linear number

201

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00 V

This parameter specifies the offset voltage for analog output 4L.

This parameter was added in Rev 5.00 and is not present in 4.xx.


Analog Offset 5L [Analog offset 5L]
Linear number:

193

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00 V

This parameter specifies the offset voltage for analog output 5L.

Analog Offset 6L [Analog offset 6L]
Linear number:

194

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00 V

This parameter specifies the offset voltage for analog output 6L.

Analog Offset 4M [Analog offset 4M]
Linear number:

202

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00 V

This parameter specifies the offset voltage for analog output 4M.

This parameter was added in Rev 5.00 and is not present in 4.xx.


Analog Offset 5M [Analog offset 5M]

Linear number:

195

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00 V

This parameter specifies the offset voltage for analog output 5M.

Analog Offset 6M [Analog offset 6M]
Linear number:

196

Minimum value:

-10.00 V

Maximum value:

9.92 V

Default value:

0.00V

This parameter specifies the offset voltage for analog output 6M.

Analog Scale 4L [Analog scale 4L]
Linear number:

203

Minimum value:

0.000

Maximum value:

10.000

Default value:

1.000

This parameter specifies the multiplication scale factor for analog output 4L.

This parameter was added in Rev 5.00 and is not present in 4.xx.

Advertising