Explicit Message Example:
Follow these steps to configure an explicit message in order to retrieve the UPS output rating information.
1. Create a new "User-Defined Data Type" called "Output Rating".
2. Go to the "Controller Tags" and create a new tag called "UPS" with an "Output Rating" data type.
3. Add a new message instruction in your routine with the following parameters. Select OK once you enter all the
required parameters.
Field
Value
Description
Message Typ eCIP
CIP Generic
CIP Message
Service Type Get
Get Attribute Single
CIP Service
Class
377
UPS Object
Instance
1
Instance 1
Attribute
1
Attribute id 1 = 1 (hex) (Appendix B)
Destination
UPS
Name given to destination tag
Path
ENET_Card
Name given to Device