Explicit message example – Rockwell Automation 1609-ENET Ethernet Network Card Quick Start User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

Chapter 2

Ethernet Mode Setup

Explicit Message Example:

Follow these steps to configure an explicit message in order to retrieve the UPS output rating information.

1. Create a new "User-Defined Data Type" called "Output Rating".

2. Go to the "Controller Tags" and create a new tag called "UPS" with an "Output Rating" data type.

3. Add a new message instruction in your routine with the following parameters. Select OK once you enter all the

required parameters.

Field

Value

Description

Message Typ eCIP

CIP Generic

CIP Message

Service Type Get

Get Attribute Single

CIP Service

Class

377

UPS Object

Instance

1

Instance 1

Attribute

1

Attribute id 1 = 1 (hex) (Appendix B)

Destination

UPS

Name given to destination tag

Path

ENET_Card

Name given to Device

 

 