Produced (input) assembly (instance 0x66) – Rockwell Automation 1609-ENET Ethernet Network Card Quick Start User Manual

Page 30

Advertising
background image

30

Rockwell Automation Publication 1609-QS002A-EN-P - May 2014

Appendix C

EtherNet/IP IO Data Mapping

Produced (Input) Assembly
(Instance 0x66)

Instance 0x66 describes another input (produced) assembly for the 1609-UPS.

Instance 0x66 – Produced (Input) Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved for Logix (Logix sets to 0xffff whenever the connection is not established. UPS sets to 0x0000.)

1
2
3

4

Reserved UPSShutDown OutputOff

UPSOff

Output

Source

Boosting

Output

Source

Reducing

Output

Source

Battery

Output

Source

Normal

5

Reserved

AC Failed

Battery

Depleted

AC Failed

BatteryLow

AC Failed

Battery OK

AC Normal

Battery

Replace

AC Normal

Battery

Weak

AC Normal

Battery

Good

6

Battery

Discharging

Battery
Resting

Battery

Charging

Battery

Floating

7

OutputBad

OverTemper

ature

OutputOver

Load

Load

Warning

Power Fail

8

Smart

Shutdown

Disconnect

InverterAbn

ormal

FanFail

ChargerFail

9

Battery Deep

Test Fail

Battery Test

Fail

General Test

Fail

Test

Passed

Test In

Progress

10

OutputVoltage (low byte)

11

OutputVoltage (high Byte)

12

OutputCurrent (low byte)

13

OutputCurrent (high byte)

14

OutputPower (low byte)

15

OutputPower (high byte)

16

OutputLoad (low byte)

17

OutputLoad (high byte)

18

OutputFrequency (low byte)

19

OutputFrequency (high byte)

20

BatteryVoltage (low byte)

21

BatteryVoltage (high byte)

22

BatteryCapacity (low byte)

23

BatteryCapacity (high byte)

24

BatteryEstimatedTime (low byte)

25

BatteryEstimatedTime (high byte)

26

BatteryTemperature (low byte)

27

BatteryTemperature (high byte)

Advertising