Chapter 3 Installation and Wiring
System Mounting
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown
below.
Allow at least 110 mm (4.33 in.) of enclosure depth to accommodate the
scanner module and the DeviceNet connector.
Panel Mounting
Mount the scanner module to a panel, using two screws per scanner module.
Use M4 or #8 panhead screws. Mounting screws are required on every
module.
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands) is prevented from falling into
the module. Debris that falls into the module could cause
damage at power up.