Automatically Configure a DeviceNet Network Chapter 4
5.
Press <Enter>
and a screen appears with the NodeComm
option highlighted.
6.
Press <Enter>
and the Node Commissioning screen appears as
shown below with the BaudRate option highlighted.
7.
Because you do not need to change the baud rate, press <SEL>
to
advance to the Address option and highlight it.
8.
Press the numbers on the key pad for the node number that you plan to
use for the device that was just installed on the DeviceNet network and
press <Enter>
.
When the address is changed an Apply Changes messages appears on
the screen.
9.
Press <SEL>
to highlight the Apply Changes message.
10.
Press <Enter>
to complete the node commissioning function.
After approximately two seconds, the 193-DNCT terminal re-initializes
and in another 10 seconds, the 193-DNCT terminal again displays the
Network Who screen. At this point, the new node appears in the table.