Hazardous Location Approval
The following information applies only to products marked 
with Hazardous Location Approval, when operating in 
hazardous locations: 
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in 
Class I Division 2 Groups A, B, C, D, Hazardous Locations and 
nonhazardous locations only. Each product is supplied with markings 
on the rating nameplate indicating the hazardous location 
temperature code. When combining products within a system, the 
most adverse temperature code (lowest “T” number) may be used to 
help determine the overall temperature code of the system. 
Combinations of equipment in your system are subject to 
investigation by the local Authority Having Jurisdiction at the time of 
installation. 
WARNING
!
EXPLOSION HAZARD -
•
Do not disconnect equipment unless power 
has been removed or the area is known to be 
nonhazardous. 
•
Do not disconnect connections to this 
equipment unless power has been removed 
or the area is known to be nonhazardous. 
Secure any external connections that mate to 
this equipment by using screws, sliding 
latches, threaded connectors, or other means 
provided with this product. 
•
Substitution of components may impair 
suitability for Class I, Division 2. 
•
If this product contains batteries, they must 
only be changed in an area known to be 
nonhazardous. 
WARNING
!
Use supply wires suitable for 30°C above 
surrounding ambient.