Connect the input cord sets to the maxum module – Rockwell Automation 1792D-4BVOD ArmorBlock MaXum 4 Input Module Series B User Manual
Page 6
 
6 ArmorBlock MaXum 4 Input Module Series B
Publication 1792D-IN017B-EN-P - September 2000
Connect the Input Cord Sets to the MaXum Module
This module uses 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the connectors on your module. Remove the 
caps and connect your cables to the appropriate ports.
Use the micro caps to cover and seal unused ports. A Pinout diagram 
for the connector is shown next.
Please refer to publication 889-5.0 for Rockwell Automation cables 
and cord sets offerings.
IMPORTANT
If the devices (sensors) connected to the input 
connections require Class 2 power to operate, the 
DeviceNet connections of this equipment must be 
powered by a Class 2 source.
ATTENTION
!
•
Make sure all connectors and caps are 
securely tightened to properly seal the 
connections against leaks and maintain IP67 
requirements.
•
For maximum noise immunity, input and 
output cable return wires must be properly 
terminated. When inputs and outputs are 
connected in loopback, return wires should 
be connected together.
•
I/O cable length should be less than 30 
meters.
1
5
3
4
2
41452
Input Micro-Connector
(View into Socket)
Pin 1 Sensor Source Voltage
Pin 2 Not Used
Pin 3 Return Logic Ground
1
Pin 4 Input
Pin 5 Not Used
1.
Logic Ground is approximately 0.4V above DeviceNet V-measured at the module.