10 ControlNet Modular Repeater Short-distance Fiber Module

Rockwell Automation Publication 1786-IN012B-EN-P - November 2010

Connect the Fiber Module

This module requires a pre-terminated zipcord wiring kit. The kits are offered in
a variety of lengths. Consult with your local distributor for attenuation
specifications before you purchase your fiber media components.

The zipcord uses a duplex cable that contains two separate fibers, one for
transmit and one for receive. If you are wiring only one channel, you can use
either channel 1 or channel 2.

1. Hold down the latch and insert the channel 1 zipcord connector into the

A and B connectors until the pins and latch lock into place.

Make certain you insert the blue pin, receive, of the zipcord connector
in A and the black pin, transmit, into B.

2. Hold down the latch and insert the other end of the duplex cable into

another module by using either channel 1 or channel 2 of the
other module.

IMPORTANT

The duplex cable is manufactured with the fiber reversed on
opposite ends. This automatically connects channel A of one unit
to channel B of the other. Do not connect more than one duplex
fiber or two simplex fibers between the same modular repeaters,
even if they are from different modules on the same repeater.

30079

Channel 1, A and B

Channel 2, A and B