Rockwell Automation 1786-RPFS ControlNet Modular Repeater Short-distance Fiber Module Installation Instruction User Manual
Page 14

14 ControlNet Modular Repeater Short-distance Fiber Module
Rockwell Automation Publication 1786-IN012B-EN-P - November 2010
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at
900 and 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
Certifications
(1)
- 1786-RPFS
Certification
(2)
Value
UL
UL Listed Industrial Control Equipment.
See UL File E65584.
CSA
CSA Certified Process Control Equipment.
See CSA File LR54689C.
CSA Certified Process Control Equipment for
Class I, Division 2 Group A, B, C, D
Hazardous Locations. See CSA File
LR69960C.
FM
FM Approved Equipment for use in Class I
Division 2 Group A,B,C,D Hazardous
Locations
Environmental Specifications - 1786-RPFS
Attribute
Value