ControlNet Modular Repeater Short-distance Fiber Module 9

Rockwell Automation Publication 1786-IN012B-EN-P - November 2010

4. If applicable, slide the module to the left to mate with the repeater

adapter or another repeater module.

You can attach a maximum of four modules to the repeater adapter, or, the
number of modules whose total power consumption does not exceed
1.6 A @ 5V DC, whichever occurs first.

If

Then

You will use a channel

Remove the protective cap from the
channel.

You will not use a channel

Keep the protective cap on to protect the
channel from dust.

You place the module in storage

Keep the protective cap on to protect the
channel from dust.

IMPORTANT

Make certain that you secure the adapter and repeater modules
with DIN-rail anchors. If you do not, loss of communication or
module damage may result.

Consult with your local distributor for attenuation specifications
before you purchase your fiber media components.

IMPORTANT

If you exceed the module or power limit, you may damage the
repeater adapter and modules.