Communicate with your armorblock lp2 i/o module – Rockwell Automation 1792D-4BT4LP INSTL INSTR ARMORBLOCK LP2 User Manual

Page 5

Advertising
background image

4 Sinking Input / 4 Output Module

5

Publication 1792D-5.26 - January 1999

Communicate With Your ArmorBlock LP2 I/O Module

This ArmorBlock module’s I/O is exchanged with the master through a
polled, change of state, or cyclic connection.

The module consumes and produces I/O data as follows:

Cyclic - allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The 4 input / 4 output module consumes the
message, updates outputs, and produces a response. The response has input
data, and the status of the Auxiliary power.

Change of state - productions occur when an input changes. If no input
change occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner module that the I/O
module is alive and ready to communicate. Consumption occurs when data
changes and the master produces new output data to the I/O module.

Refer to the table below for the word/bit definitions.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Byte

1 Byte

Polled

1 Byte

1 Byte

Change of State

1 Byte

1 Byte

Bit

07

06

05

04

03

02

01

00

Produces 0

RSVD

OPWR

RSVD

RSVD

I3

I2

I1

I0

Consumes 0

RSVD

RSVD

RSVD

RSVD

O3

O2

O1

O0

Where: RSVD= Reserved

I = Input

O = Output

OPWR= Output Power (Auxiliary Power)