Rockwell Automation 1792D-4BT4LP INSTL INSTR ARMORBLOCK LP2 User Manual
Page 6
6
4 Sinking Input / 4 Output Module
Publication 1792D-5.26 - January 1999
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our web site at http://www.ab.com/networks for producer/
consumer technology information and updates.
Byte
Bit
Description
Produces 0
00-03
04
05
06
07
Input status bits: When the bit is set (1), the input is on. Bit
00 corresponds to input 0, bit 01 corresponds to input 1, bit
02 corresponds to input 2, bit 03 corresponds to input 3.
Reserved
Reserved
Output Powr Fault (OPWR): When the bit is set (1) auxilary
power is not present.
Reserved
Consumes 0
00-03
04-07
Output bits: When the bit is set (1), the output will be turned
on. Bit 00 corresponds to output 0, bit 01 corresponds to
output 1, bit 02 to output 2, bit 03 to output 3.
Reserved