1794-TB2, 1794-TB3 and 1794-TB3S Terminal Base Wiring for the
1794-OA8

1794-TBN and 1794-TBNF Terminal Base Wiring for the 1794-OA8

Connecting Wiring for the 1794-OA8I

1. For 1794-TB2, 1794-TB3, or 1794-TB3S: Connect individual output wiring to

the even numbered terminals on the 0…15 row (A).
For 1794-TBN or 1794-TBNF: Connect individual output wiring to the
even numbered terminals on the 16…33 row (B).

2. For 1794-TB2, 1794-TB3, or 1794-TB3S: Connect the associated V AC

power lead (L1) to the corresponding odd numbered terminal on the
0…15 row (A) for each output as indicated in the table below.

For 1794-TBN or 1794-TBNF: Connect the associated V AC power (L1)
lead to the odd numbered terminals on row (C).

1794-TB2, 1794-TB3, 1794-TB3S Terminal Base Wiring for 1794-OA8I

1794-TBN and 1794-TBNF Terminal Base Wiring for the 1794-OA8I

Connecting Wiring for the 1794-OA16

1. For 1794-TB2, 1794-TB3, or 1794-TB3S: Connect individual output

wiring to numbered terminals on the 0…15 row (A) as indicated in the
table below.
For 1794-TBN: Connect individual output wiring to terminals 0…15 on
rows B and C.

2. For 1794-TB2, 1794-TB3 or 1794-TB3S: Connect the associated V AC

common (L2) lead of the output device to the corresponding numbered
terminal on the 16…33 row (B) for each output as indicated in the table
below. (The V AC common terminals of row (B) are internally connected
together.)
For 1794-TBN: Auxiliary terminal blocks are required to connect the
associated L2 common for each channel. Connect the L2 side of the load
together and then connect to L2 on the power supply.

3. Connect 120V AC power L1 to terminal 34 on the 34…51 row (C).
4. Connect 120V AC common L2 to terminal 16 on the 16…33 row (B).
5. If daisychaining power to the next terminal base, connect a jumper from

terminal 51 (120V AC L1) on this base unit to terminal 34 on the next base
unit.

6. If continuing 120V AC common (L2) to the next base unit, connect a

jumper from terminal 33 (120V AC common L2) on this base unit to
terminal 16 on the next base unit.

IMPORTANT

Individual isolated 120V AC common (L2) leads must be run externally to each
output device.

Wiring Connections for the 1794-OA8I

Output

(1)

(1)

A = Even numbered terminals 0…14 for customer connections; corresponding odd numbered 120V AC
supply L1 terminals 1…15 for customer connections from isolated power supply.

1794-TB2, 1794-TB3, 1794-TB3S

1794-TBN, 1794-TBNF

Output

Terminal

120V AC

Supply

(1)

Output

Terminal

120V AC

Supply

(2)

(2)

B = Even numbered terminals 0…14 for customer connections; C = Odd numbered 120V AC supply L1
terminals 1…15 for customer connections from isolated power supply.

0

A-0

A-1

B-0

C-1

1

A-2

A-3

B-2

C-3

2

A-4

A-5

B-4

C-5

3

A-6

A-7

B-6

C-7

4

A-8

A-9

B-8

C-9

5

A-10

A-11

B-10

C-11

6

A-12

A-13

B-12

C-13

7

A-14

A-15

B-14

C-15

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Commons

(1794-TB3 shown)

Connect 120V AC common L2 to terminal B-16.
Connect 120V AC power L1 to terminal C-34.

L2 IN

L2 OUT

Voltage

A

B

C

(Use B-33 and C-51 for daisy-chaining power to the next terminal base unit.)

L1 IN

L1 OUT

(Terminals C-35…C-50 are not present on the 1794-TB2.)

45671

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

B

C

Even Numbered I/O Terminals 0…14

Odd Numbered I/O Terminals 1…15

Connect 120V AC (L2) to terminal B-16
Connect 120V AC power (L1) to terminal C-34
Use B-33 and C-51 for daisychaining to the next terminal base

L1

L2

L1

L2

45672

IMPORTANT

Total current draw through terminal base connection is limited to 10 A.
Separate power connections to each terminal base may be necessary.

Wiring Connections for 1794-OA16

Output

Channel

1794-TB2, 1794-TB3, 1794-TB3S

1794-TBN

Output Terminal

120V AC Common (L2)

Output Terminal

(1)

0

A-0

B-17

B-0

1

A-1

B-18

C-1

2

A-2

B-19

B-2

3

A-3

B-20

C-3

4

A-4

B-21

B-4

5

A-5

B-22

C-5

6

A-6

B-23

B-6

7

A-7

B-24

C-7

8

A-8

B-25

B-8

9

A-9

B-26

C-9

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

A

B

C

(1794-TB3 shown)

Connect outputs to even numbered terminals on row (A)
Connect isolated 120V AC (L1) to odd numbered terminals on row (A)
Individual isolated 120V AC common (L2) must be run externally to each of the output devices
(Terminals C-35…C-50 are not available on the 1794-TB2.)

45673

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

+V

COM

+V

COM

B

C

Even Numbered I/O Terminals 0...14

Odd Numbered I/O Terminals 1...15

Connect outputs to even numbered terminals on row (B).
Connect isolated 120V AC (L1) to odd numbered terminals on row (C).
Individual isolated 120V AC common (L2) must be run externally to each
of the output devices.

45674