Configure the flex i/o ac output module, Specifications – Rockwell Automation 1794-OA8_OA8K_OA8I_OA16 FLEX I/O Digital AC Output Modules Installation Instructions User Manual

Page 4

Advertising
background image

4

Publication 1794-IN103B-EN-P - May 2011

1794-TB2, 1794-TB3, 1794-TB3S Terminal Base Wiring for 1794-OA16

1794-TBN Terminal Base Wiring for 1794-OA16

Configure the FLEX I/O AC Output Module

Specifications

10

A-10

B-27

B-10

11

A-11

B-28

C-11

12

A-12

B-29

B-12

13

A-13

B-30

C-13

14

A-14

B-31

B-14

15

A-15

B-32

C-15

120V AC L1
power

Connect V AC L1 to C-34.

1794-TB3, 1794-TB3S – Power terminals C-34…C-51 are internally connected together.

1794-TB2 and 1794-TBN – C-34 and C-51 are internally connected together.

120V AC L2
common

Connect 120V AC common L2 to terminal B-16.

1794-TB3, 1794-TB3S – 120V AC common L2 terminals B-16…B-33 are internally connected together.

1794-TB2, 1794-TBN – 120V AC common L2 terminals B-16 and B-33 internally connected together.

(1)

Auxiliary terminal blocks are required to connect the associated L2 common for each channel when
using a 1794-TBN terminal base with the 1794-OA16.

Image Table Memory Map for the 1794-OA8, 1794-OA8K and 1794-OA8I

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Not used – set to 0

Write

Not used – set to 0

O7

O6

O5

O4

O3

O2

O1

O0

Where: O = Output number

Wiring Connections for 1794-OA16

Output

Channel

1794-TB2, 1794-TB3, 1794-TB3S

1794-TBN

Output Terminal

120V AC Common (L2)

Output Terminal

(1)

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Commons

(1794-TB3 shown)

Connect 120V AC common L2 to terminal B-16.
Connect 120V AC power L1 to terminal C-34.

L2 IN

L2 OUT

Voltage

A

B

C

(Use B-33 and C-51 for daisy-chaining power to the next terminal base unit.)

L1 IN

L1 OUT

(Terminals C-35…C-50 are not present on the 1794-TB2.)

Outputs

45675

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

51

33

34

B

C

Even Numbered I/O Terminals 0…14

Odd Numbered I/O Terminals 1…15

Connect 120V AC (L2) to terminal B-16
Connect 120V AC power (L1) to terminal C-34
Use B-33 and C-51 for daisychaining to the next terminal base

L1

L2

L1

L2

45676

Image Table Memory Map for the 1794-OA16

Dec

15

14

13

12

11

10

09

08

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Not used - set to 0

Write

O15

O14

O13

O12

O11

O10

O9

O8

O7

O6

O5

O4

O3

O2

O1

O0

Where: O = Output number

Specifications for 1794-OA8, 1794-OA8K and 1794-OA8I

Attribute

1794-OA8, 1794-OA8K

1794-OA8I

Number of outputs

8, (1 group of 8), nonisolated

8, isolated

Module location

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN and 1794-TBNF

Output voltage range

85V AC, min

120V AC, nom

132V AC, max

Output current rating

4.0A (8 outputs @ 500 mA)

On-state current

5.0 mA per output min

500 mA per output max @ 55 °C (sufficient to operate an Allen-Bradley
Bulletin 500 NEMA size 3 motor starter)

750 mA per output max @ 35 °C

1.0A on 4 nonadjacent outputs, 500 mA on the remaining 4 outputs @ 30 °C

NOTE: Below 50 mA the voltage drop across the module will be higher and
the voltage waveform may have some small oscillation (less than 5V).

Voltage drop,
on-state, max

1.0V @ 0.5A

Leakage current,
off-state, max

2.25 mA

Surge current

7A for 40 ms, repeatable every 8 s

Output signal delay

(1)

Off to On

On to Off

(1)

Output signal delay is the time from receipt of an output on or off command to the output actually
turning on or off.

1/2 cycle, max

1/2 cycle, max

Power dissipation, max

4.1W @ 0.5A

6.3W @ 0.75A

6.3W @ 1.0A

Thermal dissipation

14.0 BTU/hr @ 0.5 A

21.2 BTU/hr @ 0.75 A

21.4 BTU/hr @ 1.0 A

FlexBus current

80 mA @5V DC

Fusing

(2)

(2)

Module outputs are not fused. Fusing is recommended. If fusing is desired, you must supply external
fusing or use the 1794-TBNF terminal base, if recommended.

1.6A, 250V AC slow-blow, Littelfuse 23901.6; San-O SD6-1.6 (1.6A fuses
come preinstalled in 1794-TBNF terminal base units.)

Specifications for 1794-OA16

Attribute

Value

Number of outputs

16, nonisolated

Module location

1794-TB2, 1794-TB3, 1794-TB3S and 1794-TBN3

(3)

Mounting

See derating curve

Output voltage range

74V AC min, 47…63 Hz

120V AC nom, 47…63 Hz

132V AC max, 47…63 Hz

Output current rating

4.0A (16 outputs @ 250 mA)

Attention: If using 0.5A outputs, alternate wiring so that no
two 0.5 A outputs are next to each other.

On-state current

5.0 mA per output, min

500 mA per output @ 55 °C, max

NOTE: Below 50 mA the voltage drop across the module will
be higher and the voltage waveform may have some small
oscillation (less than 5V).

On-state voltage drop, max

1.5V @ 0.5 A

Off-state leakage current, max

2.25 mA

Surge current

7 A for 40 ms, repeatable every 8 s

Output signal delay

(1)

Off to On

On to Off

1/2 cycle, max

1/2 cycle, max

Power dissipation, max

4.7W @ 0.5A

Thermal dissipation

16.1 BTU/hr @ 0.5 A

FlexBus current

80 mA @ 5V DC

Fusing

(2)

2.5A, 150V AC normal blow, MQ2

Advertising