5

Publication 1794-IN103B-EN-P - May 2011

Derating Curve for 1794-OA16

(1)

Auxiliary terminal blocks are required to connect the associated 120V AC common for each channel
when using the 1794-TBN terminal base with the 1794-OA16.

(2)

Output signal delay is the time from receipt of an output on or off command to the output actually
turning on or off.

(3)

Module outputs are not fused. Fusing is recommended. If fusing is desired, you must supply external
fusing or use the 1794-TBNF terminal base, if recommended.

General Specifications

Attribute

Value

Terminal base screw torque

Determined by installed terminal base

Dimensions (with module
installed), HxWxD

94 x 94 x 69 mm

(3.7 x 3.7 x 2.7 in.)

Indicators (field side
indication, logic driven)

8 yellow status indicators – for 1794-OA8, 1794-OA8K

8 yellow status indicators – for 1794-OA8I

16 yellow status indicators – for 1794-OA16

Supply voltage or

voltage ranges

FlexBus: 5V DC, 80 mA

Output: 120V AC, 50/60 Hz, 0.5 A, Pilot Duty, 4 A total

Isolation voltage

120V (continuous), Basic Insulation Type, field side to backplane

No isolation between individual channels

Type tested @ 1250V AC for 60 s

Pilot Duty Rating

5 A Inrush

Keyswitch position

8

Enclosure type rating

None (open-style)

North American Temp Code

T4A – for 1794-OA8, 1794-OA8K, 1794-OA8I only

T4 – for 1794-OA16 only

IEC temp code

T4 – for 1794-OA8K only

Wire size

Determined by installed terminal base

Wiring

Category

(1)

2 – on signal ports

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Temperature,
surrounding air, max

55 °C (131 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

Radiated RF
immunity

(1794-OA8, 1794-OA8K)

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

(1794-OA8I)

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

(1794-OA16)

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF
immunity

(1794-OA8, 1794-OA8K, 1794-OA8I)

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…30 MHz

(1794-OA16)

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge
withstand

IEEE C37.90.1:

2.5 kV

Certifications

Certifications
(when product is

marked)

(1)

Value

UL

UL Listed Industrial Control Equipment. See UL File E65584.

CSA

(for 1794-OA8,
1794-OA8K, and
1794-OA8I only)

CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2

Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CSA

(for 1794-OA16 only)

CSA Certified Process Control Equipment. See CSA File LR93701.
CSA Certified Process Control Equipment for Class I, Division 2

Group A,B,C,D Hazardous Locations. See CSA File LR93701.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

(for 1794-OA8K only)

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA nC IIC T4 X

(1)

See the Product Certification link at

http://www.ab.com

for Declarations of Conformity, Certificates,

and other certification details.

Mounting

Temperature, max.

Normal horizontal

55 °C

Other mounting positions (including inverted horizontal, vertical)

51 °C

Environmental Specifications

Attribute

Value

0

72

10

20

30

40

50

55

60

V in

On-state

V

oltage

(V AC)

Ambient Temperature

oC

The area within the curve represents the safe operating range for the module under
various conditions of user supplied 120V AC supply voltages and ambient temperatures.

= Other mounting positions (including inverted horizontal, vertical)

safe operating range

80

88

96

102

110

115

120

132

51

= Normal mounting safe operating range. Includes

130

45677