Appendix
E
Module Configuration by Using a
MicroLogix 1500 System and RSLogix 500
Software
This appendix examines the 1769-IT6 module’s addressing scheme and describes
module configuration by using RSLogix 500 and a MicroLogix 1500 controller.
Module Addressing
This memory map shows the input and configuration image tables for the
module. For detailed information on the image table, see
.
Figure 55 - Memory Map for Input and Configuration Image Tables
Channel 0 Data Word
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
General/Open-Circuit Status Bits
Over-/Under-range Bits
Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word
I:e.0
I:e.1
I:e.2
I:e.3
I:e.4
I:e.5
Word 0
Word 1
Word 2
Word 3
Address
Input Image
8 words
Configuration
File
7 words
Slot e
Slot e
Input Image
File
Configuration
File
Memory Map
Bit 15
Bit 0
Channel 4 Data Word
Channel 5 Data Word
Word6
Word 7
I:e.6
I:e.7
Channel 4 Configuration Word
Channel 5 Configuration Word
Word 4
Word 5
Enable/Disable Cyclic Calibration
Word 6
Refer to