Mounting, Minimum spacing, Panel mounting – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual
Page 28: Minimum spacing panel mounting

28
Rockwell Automation Publication 1769-UM004B-EN-P - March 2010
Chapter 3 Installation and Wiring
8.
Lock the end cap bus terminator (6).
Mounting
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, and so
forth. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown
below.
Panel Mounting
Mount the module to a panel by using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap respectively must be
used to terminate the end of the bus.
ATTENTION: During panel or DIN rail mounting of all devices, be sure
that all debris (metal chips, wire strands) is kept from falling into the
module. Debris that falls into the module could cause damage at
powerup.
Host Controller
Compact I/O
Compact I/O
Compact I/O
Compact I/O
Compact I/O
En
d Cap
Side
Side
Top
Bottom