Extended-error information field, See configuration – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual
Page 79

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010
79
Diagnostics and Troubleshooting Chapter 5
Extended-error Information Field
Check the extended error information field when a non-zero value is present in
the module error field. Depending upon the value in the module error field, the
extended error information field can contain error codes that are module-specific
or common to all 1769 analog modules.
Hardware Errors
General or module-specific hardware errors are indicated by module error code
001. See
Table 11 on page 80
.
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values, the
module generates a critical error.
Table 11 on page 80
lists the possible module-specific configuration error codes
defined for the modules.
TIP
If no errors are present in the module error field, the extended error
information field is set to zero.