Specifications – Rockwell Automation 1771-OBDS DC(10-40V)Current Limiting Input Module Installation Instructions User Manual

Page 13

Advertising
background image

DC (10-40V) Current Limiting Output Module

13

Publication 1771ĆIN033B-EN-P - July 2002

Outputs per Module

16

Module Location

1771ĆA1B, thru ĆA4B or later I/O chassis

Output Voltage Range

10 to 40V dc

Output Current Rating

1A per output Ć not to exceed 8A per module, Pilot duty.

See derating curve below.

On State Voltage Drop (max.)

1.5V at rated current

Off State Leakage Current (max.)

0.5mA per output

Signal Delay

Off to On

On to Off

1.0ms

1.0ms

Power Dissipation

14 Watts (max.), 2 Watts (min.)

Power Dissipation - adjacent slot

10 Watts (max.)

Thermal Dissipation

47.8 BTU/hr (max.), 6.9 BTU/hr (min.)

Backplane Current

300mA @ 5V dc +5%

Isolation Voltage

Tested to withstand 500V for 60s.

Conductors

Wire Size

Category

14 AWG (2.5mm

2

) stranded copper rated at 60

o

Cor greater

3/64 inch (1.2mm) insulation (max)

2

1

Environmental Conditions

Operating

Temperature

IEC60068-2-1 (Test Ad, Operating Cold)

IEC60068-2-2 (Test Bd, Operating Dry Heat)

IEC60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0

o

to 60

o

C)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal

Shock)

-40 to 185°F (-40 to 85

o

C)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC61000-4-2

4kV indirect discharges

Radiated RF Immunity

IEC61000-4-3

10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

EFT/B Immunity

IEC61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC61000-4-5

+1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Specifications