DC (10-40V) Current Limiting Output Module

8

Publication 1771ĆIN033B-EN-P - July 2002

Actual wiring runs in this direction.

Output 00

Output 01

Output 02
Output 03
Output 04
Output 05

Output 06
Output 07
Output 10
Output 11

Output 12

Output 13

Output 14
Output 15

Output 16
Output 17

Output

Device

dc

User

dc

Supply

+dc

Ćdc

+dc

+dc
+dc

+

+

Ć

Ć

A

B

C

D

01

02

03

04

05

06

07
10

11

12
13

14
15

16

17

00

E

10419ĆI

You must supply dc at terminals A through D on the wiring arm. You
need four dc connections to accommodate the total required surge
rating on the module without overstressing any single connection on
the field wiring arm. Jumper all dc connections together to prevent
module damage. Connect terminal E to dc common.

!

ATTENTION

Observe proper polarity, as indicated in the
connection diagram with dc power connections.
Reverse polarity, or application of ac voltage,
could damage the module.