Rockwell Automation 1771-OBDS DC(10-40V)Current Limiting Input Module Installation Instructions User Manual

Page 14

Advertising
background image

DC (10-40V) Current Limiting Output Module

14

Publication 1771ĆIN033B-EN-P - July 2002

Keying

Between 10 and 12

Between 22 and 24

Fuse

12A, 250V rectifier fuse (1/4 x 1Ć1/4 inch), Bussman GBB12, IEC127

Type F (black)

Field Wiring Arm

Catalog Number 1771ĆWH

Wiring Arm Screw Torque

9 pound-inches (1.0Nm)

Agency Certification

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment for Class I,

Division 2 Group A, B, C, D Hazardous Locations

CE

2

European Union 89/336/EECEMCDirective,

compliant with:

EN 50082-2, Industrial Immunity

EN 61236, Meas./Control/Lab., Industrial Requirements

EN 61000-6-2, Industrial Immunity

EN 61000-6-4, Industrial Emissions

EEx

2

European Union 94/9/EECATEX Directive, compliant with:

EN 50021, Potentially Explosive Atmospheres, Protection n"

C-Tick

2

Australian Radiocommunications Act, compliant with:

AS/NZS 2064, Industrial Emissions

1

You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial

Automation Wiring and Grounding Guidelines.

2

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details

European Zone 2 Certification

This equipment is intended for use in potentially explosive atmospheres as defined by European

Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been

found to comply with the Essential Health and Safety Requirements relating to the design and

construction of Category 3 equipment intended for use in potentially explosive atmospheres,

given in Annex II to this Directive. The examination and test results are recorded in confidential

report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by

compliance with EN 50021 (1999).

IMPORTANT

Observe the following additional Zone 2 certification requirements:

• This equipment is not resistant to sunlight or other sources of UV

radiation.

• The secondary of a current transformer shall not be open-circuited when

applied in Class I, Zone 2 environments.

• Equipment of lesser Enclosure Type Rating must be installed in an

enclosure providing at least IP54 protection when applied in Class I, Zone

2 environments.

• This equipment shall be used within its specified ratings defined by

Allen-Bradley.

• Provision shall be made to prevent the rated voltage from being exceeded

by transient disturbances of more than 40% when applied in Class I, Zone

2 environments.

Advertising