10

FLEX Integra 16 Sink Input Module

Publication 1793-5.8 - December 1999

Specifications - 16 Input Module Cat. No. 1793-IB16 and -IB16S

Module Type

16 digital input - sinking
1793-IB16 - screw-cage terminations
1793-IB16S - spring-clamp terminations

Module Location

DIN rail mounting

Number of Channels

16 (1 group of 16, nonisolated, sinking)

On-state Voltage

10V dc minimum
24V dc nominal
31.2V dc maximum

On-state Current

2mA minimum
8.8mA nominal at 24V dc
12.1mA maximum

Off-state Voltage

5V dc maximum

Off-state Current

1.5mA minimum

Input Impedance

2.5K

Ω maximum

Isolation Voltage

100% tested at 850V dc for 1s between user and system.
No isolation between individual channels

Input Filter Time - selectable

Off to On

On to Off

Minimum 1ms plus selected filter time of:
250

μs, 500μs, 1ms, 2ms, 4ms, 8ms, 16ms, or 32ms

250

μs, 500μs, 1ms, 2ms, 4ms, 8ms, 16ms, or 32ms

Default = 250

μs selectable thru output image table

Flexbus Current

25mA maximum

Power Dissipation

6.1W @ 31.2V dc

Thermal Dissipation

20.8 BTU/hr @ 31.2V dc

Indicators

16 yellow channel status indicators

External dc Power Voltage

19.2-31.2V dc (5% ac ripple)

See Derating Curve.

Dimensions

Inches

(Millimeters)

2.72H x 3.7D x 3.2W
(69H x 94D x 80W)

Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Nonoperating

Vibration

0 to +55

o

C (32 to +131

o

F)

-40 to +85

o

C (-40 to +185

o

F)

5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+1)ms pulse width
Tested to 50g peak acceleration, 11(+1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6

Conductors

Wire Size

Category

12 gauge to 18 gauge (4mm

2

to 0.75mm

2

)

stranded wire rated @ 75

o

C minimum

3/64 in (1.2mm) maximum insulation
2

1

Advertising