FLEX Integra 16 Sink Input Module

7

Publication 1793-5.8 - December 1999

Setting the Input Delay Time

You can select the input delay time (DT) for channels 00 thru 011, and
channels 12-15. Select the input delay time by setting the corresponding
bits in the output image table (complementary word) for the module.

For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits05, 04, 03, 02, 01 and 00 as shown below.

Input Delay Times

Important: Input and output wiring must be in accordance with Class I,

Division 2 wiring methods and in accordance with the
authority having jurisdiction.

02

01

00

Filter Time for Inputs 00-11

Selected
Filter Time

05

04

03

Filter Time for Inputs 12-15

0

0

0

Filter Time 0 (default)

250

μs

0

0

1

Filter Time 1

500

μs

0

1

0

Filter Time 2

1ms

0

1

1

Filter Time 3

2ms

1

0

0

Filter Time 4

4ms

1

0

1

Filter Time 5

8ms

1

1

0

Filter Time 6

16ms

1

1

1

Filter Time 7

32ms

15 14 13 12

11 10 09 08 07 06 05 04 03 02 01 00

1

0

0

= 44 Octal or 36 decimal

Write delay time on system startup.

Write DT to complement

of input module.

Fill File
Source

Destination
Length

3

#O:010

1

I:000

00

FLL

O:010

Dec.

41335B

1

0

0

DT 00-11

DT 12-15