Setting the Input Delay Time
You can select the input delay time (DT) for channels 00 thru 011, and
channels 12-15. Select the input delay time by setting the corresponding
bits in the output image table (complementary word) for the module.
For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits05, 04, 03, 02, 01 and 00 as shown below.
Input Delay Times
Important: Input and output wiring must be in accordance with Class I,
Division 2 wiring methods and in accordance with the
authority having jurisdiction.
02
01
00
Filter Time for Inputs 00-11
Selected
Filter Time
05
04
03
Filter Time for Inputs 12-15
0
0
0
Filter Time 0 (default)
250
μs
0
0
1
Filter Time 1
500
μs
0
1
0
Filter Time 2
1ms
0
1
1
Filter Time 3
2ms
1
0
0
Filter Time 4
4ms
1
0
1
Filter Time 5
8ms
1
1
0
Filter Time 6
16ms
1
1
1
Filter Time 7
32ms
15 14 13 12
11 10 09 08 07 06 05 04 03 02 01 00
1
0
0
= 44 Octal or 36 decimal
Write delay time on system startup.
Write DT to complement
of input module.
Fill File
Source
Destination
Length
3
#O:010
1
I:000
00
FLL
O:010
Dec.
41335B
1
0
0
DT 00-11
DT 12-15