Specifications – Rockwell Automation 1771-OWNA Contact Output Module Installation Instructions User Manual

Page 13

Advertising
background image

Specifications

Contact Output Module

13

Publication 1771-IN038B-EN-P - August 2002

Outputs per module

32 (4 groups of 8)

Module Location

1771ĆA1B thru ĆA4B or later I/O Chassis, 1771ĆAM, ĆAM1 I/O

Chassis

Voltage Rating

24 Ć 138V ac rms; 24 Ć 125V dc

Current Rating

1

Max. per channel

Max. per module

Max. per group

1A continuous (derate linearly 0.033A/

o

Cabove 45

o

C)

12A (derate linearly 0.4A/

o

Cabove 45

o

C)

4A (derate linearly 0.133A/

o

Cabove 45

o

C)

Maximum Surge Current

1A (max) per output (at rated power)

2

Output Contact Power Rating

30W per output (resistive) maximum at 45

o

C, 15W at 60

o

C

Minimum Contact Load

10mA

Operate/Release Time

5ms (+1ms) typical

Bounce Time

1ms (max)

Switching Frequency

10Hz (max)

Power Dissipation

All relays off: 15mW; All relays on: 13.7W (max.)

Thermal Dissipation

All relays off: 0.05 BTU/hr; All relays on: 46.7 BTU/hr (max.)

Backplane Current

2.5A maximum; 1.8A nominal

Isolation Voltage

Tested to withstand 1000V for 60s.

Interconnect Cable Length

1000 ft. (304.8 meters)

Conductors

Wire Size

Category

14-22 AWG (2.5-0.5mm

2

) (max) stranded copper rated at 60

o

Cor

greater

3/64 inch (1.2mm) insulation (max)

2

3

Environmental Conditions

Operating

Temperature

IEC60068-2-1 (Test Ad, Operating Cold)

IEC60068-2-2 (Test Bd, Operating Dry Heat)

IEC60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0

o

to 60

o

C)

Storage Temperature

IEC60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal

Shock)

-40 to 185°F (-40 to 85

o

C)

Relative Humidity

IEC60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC61000-4-2

4kV contact discharges

Radiated RF Immunity

IEC61000-4-3

10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

10V/m with 200Hz 50% pulse 100% AM at 900MHz

EFT/B Immunity

IEC61000-4-4

+1kV @ 5kHz on signal ports

Specifications continued on next page.