Rockwell Automation 1771-OWNA Contact Output Module Installation Instructions User Manual

Page 9

Advertising
background image

Contact Output Module

9

Publication 1771-IN038B-EN-P - August 2002

Table A

Wiring Connections for the 1771-OWNA Contact

Output Module

Terminal

Number

Function

Terminal

Number

Function

1

Common 0

21

Common 2

2

Output 00

22

Output 00

3

Output 01

23

Output 01

4

Output 02

24

Output 02

5

Output 03

25

Output 03

6

Output 04

26

Output 04

7

Output 05

27

Output 05

8

Output 06

28

Output 06

9

Output 07

29

Output 07

10

Not used

30

Not used

11

Common 1

31

Common 3

12

Output 10

32

Output 10

13

Output 11

33

Output 11

14

Output 12

34

Output 12

15

Output 13

35

Output 13

16

Output 14

36

Output 14

17

Output 15

37

Output 15

18

Output 16

38

Output 16

19

Output 17

39

Output 17

20

Not used

40

Not used

If using multiple power supplies, do not exceed the specified isolation voltage.

!

ATTENTION

Observe proper polarity with dc power
connections. Reverse polarity, or application of ac
voltage could damage the module.

Advertising