Select the Proper Resistor
Use 82 resistors if the network operates at 230.4 kbps or if the network
operates at 57.6 kbps, or 115.2 kbps and none of the devices in this table are
present. The maximum number of devices on the network is 32.
Use 150 resistors if the network contains any of the devices in this table, or if
the network operates at 57.6 kbps or 115.2 kbps and you do not require the
network to support more than 16 devices.
Device Resistors
Cat. No.
Series
1747-ASB
All
1771-AS
All
1771-ASB
Series A
1775-S5
All
1794-ASB
All
1771-DCM
All
1771-SN
All
1772-SD
All
1772-SD2
All
1775-S4A
All
1775-S4B
All
1775-SR5
All
Baud Rate Cable Limits
Baud Rate
Maximum Cable Length
57.6 Kbaud
3048 m (10000 ft)
115.2 Kbaud
1524 m (5000 ft)
230.4 Kbaud
762 m (2500 ft)