Select the Proper Resistor

Use 82  resistors if the network operates at 230.4 kbps or if the network
operates at 57.6 kbps, or 115.2 kbps and none of the devices in this table are
present. The maximum number of devices on the network is 32.

Use 150 resistors if the network contains any of the devices in this table, or if
the network operates at 57.6 kbps or 115.2 kbps and you do not require the
network to support more than 16 devices.

Device Resistors

Cat. No.

Series

1747-ASB

All

1771-AS

All

1771-ASB

Series A

1775-S5

All

1794-ASB

All

1771-DCM

All

1771-SN

All

1772-SD

All

1772-SD2

All

1775-S4A

All

1775-S4B

All

1775-SR5

All

Baud Rate Cable Limits

Baud Rate

Maximum Cable Length

57.6 Kbaud

3048 m (10000 ft)

115.2 Kbaud

1524 m (5000 ft)

230.4 Kbaud

762 m (2500 ft)