20 ControlLogix EtherNet/IP Module

Rockwell Automation Publication 1756-IN606B-EN-P - April 2010

Status Indicators

Indicator

Status

Description

NET

Off

The module is not powered. Verify that there is
chassis power and that the module is completely
inserted into the chassis and backplane.
The module does not have a valid IP address.
Make sure the module has been configured with
a valid IP address.

Flashing green

The module has an IP address, but has no
established connections.

Green

The module has an IP address and at least one
established connection.

Red

The module is attempting to use an IP address
already in use on the network. Assign a unique IP
address to the module.

Link

Off

The module is not ready to communicate. Verify
that the module has power.

Green

The module is ready to communicate.

Flashing green

The module is communicating over the network.

OK

Off

Verify that the module has 24V DC chassis
power and that the module is completely
inserted into chassis and backplane.

Flashing green

The module is not configured.

Green

The module is operating correctly.

Flashing red

The module detected a recoverable fault. A
configuration error may have caused the fault.
Check the module configuration. If necessary,
reconfigure the module.

Red

The module detected an unrecoverable fault.
Cycle power to the module. If this does not clear
the fault, replace the module.

Red and alphanumeric
display scrolls 'Image
Update Needed'

Update the firmware image. Once the image is
updated, cycle power. If this does not clear the
fault, replace the module.

Flashing red and green

The module is performing a power-up self-test.