Interpret status indicators – Rockwell Automation 1771-IL INSTL.INSTR.ISOL ANALOG INPUT User Manual

Page 10

Advertising
background image

Isolated Analog Input Module

10

Publication 1771Ć5.51 - October 1996

Default Configuration

If a write block of with all zeroes is sent to the module, the default
selections will be:

1 to 5V dc or 4 to 20mA (depends on voltage/current selection
jumper setting)

BCD data format

no real time sampling (RTS)

no digital filter

no scaling

no alarms

The front panel of the isolated analog input module contains a green
RUN indicator and a red FAULT indicator. At power-up, the module
momentarily turns on both indicators as a lamp test, then checks for:

correct RAM operation

EPROM operation

EEPROM operation

a valid write block transfer with configuration data

If there is no fault, the red indicator turns off.

The green indicator comes on when the module is powered. It will
flash until the module is programmed. If a fault is found initially or
occurs later, the red fault indicator lights. The module also reports
status and specific faults (if they occur) in every transfer of data
(BTR) to the PC processor. Monitor the green and red indicators and
status bits in word 1 of the BTR file when troubleshooting your
module.

RUN

FLT

10528ĆI

Green RUN indicator

Red FAULT indicator

ISOLATED

ANALOG INPU

T

Interpret Status Indicators