Isolated Analog Input Module

6

Publication 1771Ć5.51 - October 1996

Connect your I/O devices to the field wiring arm (cat. no. 1771-WF)
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Analog Source

Analog Source

Connection Diagram for the Isolated Analog Input Module

(cat. no. 1771ĆIL/C)

Channel 3

Channel 2

Channel 1

Channel 4

Channel 7

Channel 6

Channel 5

Channel 8

Ground

Ground

Field Wiring Arm

Cat. No. 1771ĆWF

18

17

16

1

15
14
13

12

11

10

9
8

7

6

5
4

3

2

18

17

16

1

15

14
13

12

11

10

9

8

7

6

5
4

3

2

11846ĆI

NOTE: The 1771ĆIL/C module does not supply loop power for loop powered

analog sources (transmitters, transducers, etc.). Loop power must be

supplied by the user.

+

+

Connect Wiring to the

Field Wiring Arm