The module has configuration jumpers for determining the input type
(voltage or current) for each input. The module is shipped with the
configuration jumpers positioned for voltage mode.
You can
select either voltage or current for each input.

Keythe Backplane

Connector

Place your module in any slot in the chassis
except the leftmost slot which is reserved for
processors or adapters.

ATTENTION: Observe the
following precautions when
inserting or removing keys:

insert or remove keys with
your fingers

make sure that key placement
is correct

Incorrect keying or the use of a
tool can result in damage to the
backplane connector and possible
system faults.

!

Position the keying bands in the backplane connectors to correspond to

the key slots on the module.

Place the keying bands:

between 10 and 12

between 32 and 34

You can change the position of these bands if

subsequent system design and rewiring makes

insertion of a different type of module necessary.

Upper

Connector

11022ĆI

I/O chassis

Setting the Configuration

Jumpers

Remove the four screws securing the side cover to

the module and remove the covers.

19805

1

Reposition the configuration jumpers associated with each input

channel according to your requirements.

2

The module is shipped with each channel set for voltage mode. If

current mode is desired, you must set a jumper on the functional

analog block (FAB) on the module. You can mix voltage mode and

current mode settings.

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Configuration

Jumper

FAB

Voltage

Mode

Current

Mode

Front view

of module

circuit board

Top

Enlarged View

Reposition the cover and secure with the four

screws removed in step 1.

19813

3