Input specifications – Rockwell Automation 1762-IA8 MICROLOGIX 120 VAC INPUT MODULE User Manual
Page 12

12
MicroLogix™ 1762-IA8 120V ac Input Module
1762-IN002A-US-P
Input Specifications
Specification
1762-IA8
Voltage Category
100/120V ac
Operating Voltage Range
79V ac to 132V ac at 47 Hz to 63 Hz
Number of Inputs
8
Bus Current Draw (max.)
50 mA at 5V dc (0.25W)
Heat Dissipation (max.)
2.0 Total Watts
Signal Delay (max.)
On Delay: 20.0 ms
Off Delay: 20.0 ms
Off-State Voltage (max.)
20V ac
Off-State Current (max.)
2.5 mA
On-State Voltage (min.)
79V ac (min.) 132V ac (max.)
On-State Current
5.0 mA (min.) at 79V ac 47 Hz
12.0 mA (nominal) at 120V ac 60 Hz
16.0 mA (max.) at 132V ac 63 Hz
Inrush Current (max.)
250 mA
Nominal Impedance
12K
Ω
at 50 Hz
10K
Ω
at 60 Hz
IEC Input Compatibility
Type 1+
Power Supply Distance Rating
6
Isolated Groups
Group 1: inputs 0 to 7 (internally connected commons)
Input Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1517V ac for 1
sec. or 2145V dc for 1 sec.
132V ac working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
1
Product Type Code
7
Product Code
114