MicroLogix™ 1762-IA8 120V ac Input Module

5

1762-IN002A-US-P

Mounting

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow
50.8 mm (2 in.) of space
on all sides for adequate
ventilation, as shown:

!

ATTENTION: Do not remove protective debris strip until after
the module and all other equipment near the module is mounted and
wiring is complete. Once wiring is complete and the module is free
of debris, carefully remove protective debris strip. Failure to
remove strip before operating can cause overheating.

Note:

1762 expansion I/O may be mounted horizontally only.

!

ATTENTION: During panel or DIN rail mounting of all devices,
be sure that all debris (metal chips, wire strands, etc.) is kept from
falling into the module. Debris that falls into the module could
cause damage when power is applied to the module.

MicroLogix

1200

1762 I/O

1762 I/O

1762 I/O

Side

Side

Top

Bottom