FLEX I/O Remote I/O Adapter Modules 1

Publication 1794-IN098E-EN-P - January 2011

Installation Instructions

FLEX I/O Remote I/O Adapter Modules

Cat. No. 1794-ASB and 1794-ASBK Series E;
1794-ASB2, Series D

(Modules with a K in the last position of the catalog number are conformally
coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3
Environment.)

European Hazardous Location Approval

The following modules are European Zone 2 approved: 1794-ASB and
1794-ASBK Series E; 1794-ASB2, Series D

IMPORTANT

Do not use these adapters (1794-ASB and 1794-ASBK Series E; 1794-ASB2,
Series D) with the Classic PLC-5/15 or PLC-5/25 processors. Improper operation
of the remote I/O can result.

Important User Information

Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls (Publication

SGI-1.1

available from your local Rockwell

Automation sales office or online at

http://www.literature.rockwellautomation.com

)

describes some important differences between solid state equipment and hard-wired
electromechanical devices. Because of this difference, and also because of the wide variety
of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on
the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.

Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury
or death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and
understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions
help you:

• identify a hazard
• avoid a hazard
• recognize the consequence

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1),
at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there may be difficulties with
electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.

This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of flame, complying
with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The
interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional information
regarding specific enclosure type ratings that are required to comply with certain
product safety certifications.

In addition to this publication, see:

• Industrial Automation Wiring and Grounding Guidelines, Rockwell

Automation publication

1770-4.1

, or additional installation requirements.

• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the

degrees of protection provided by different types of enclosure.

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:

• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in

use.

ATTENTION

Power wiring must be less than 10 m (33 ft) in length.

ATTENTION

FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN
rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding. Secure DIN
rail to mounting surface approximately every 200 mm (7.8 in.) and use
end-anchors appropriately.

ATTENTION

Do not remove or replace an adapter module while power is applied.
Interruption of the backplane can result in unintentional operation or machine
motion.

ATTENTION

To reduce susceptibility to noise, power analog modules and digital modules
from separate power supplies.

European Zone 2 Certification (The following applies when the product bears the Ex
Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by European
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3 equipment intended for use
in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements:

• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment must be installed in an enclosure providing at least IP54

protection when applied in Zone 2 environments.

• This equipment shall be used within its specified ratings defined by

Rockwell Automation.

• Provision shall be made to prevent the rated voltage from being exceeded

by transient disturbances of more than 40% when applied in Zone 2
environments.

• Secure any external connections that mate to this equipment by using

screws, sliding latches, threaded connectors, or other means provided
with this product.

• Do not disconnect equipment unless power has been removed or the area

is known to be nonhazardous.

Advertising