Back cover – Rockwell Automation 1794-ASB/E_ASB2/D_ASBK/E_ASB2K/D Remote I/O Adapter Modules Installation Instructions User Manual
Page 6
Publication 1794-IN098E-EN-P - January 2011
6
Supersedes Publication 1794-IN098D-EN-P- March 2005
Copyright © 2011 Rockwell Automation, Inc. All rights reserved.
Mounting Dimensions
Environmental Conditions
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Temperature,
surrounding air, max
55 °C (131 °F)
Temperature,
nonoperating
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Un-packaged
Damp Heat):
5…95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity
IEC 61000-4-2:
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
3 V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communications ports
Surge Transient
Immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports
Conducted RF
Immunity
IEC 61000-4-6:
10 Vrms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Certifications (when product is marked)
(1)
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CSA
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2
Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 X
Publications
Installation Instructions
; User Man
(1)
See the Product Certification link at
for Declarations of Conformity, Certificates, and other certification
details.
Mounting Dimensions
(3.4)
87
(0.83)
21
(1.4)
35
(2.3)
59
(2.0)
50
(1.2)
28
(2.7)
69
(3.4H x 2.7W x 2.7D)
87H x 69W x 69D
1794-ASB/E
1794-ASB2/D
(inches)
millimeters
(3.4)
87
A
B
C
A = Mounting hole dimensions for optional mounting kit
B = DIN rail
C = Secure DIN rail approximately every 200 mm