Mounting Dimensions

Environmental Conditions

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Temperature,
surrounding air, max

55 °C (131 °F)

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Un-packaged

Damp Heat):

5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10 V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz

10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

3 V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:

±2 kV line-earth(CM) on communications ports

Conducted RF
Immunity

IEC 61000-4-6:

10 Vrms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Certifications (when product is marked)

(1)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2

Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA IIC T4 X

Publications

Installation Instructions

1794-IN098

; User Manual

1794-UM009

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates, and other certification

details.

Mounting Dimensions

(3.4)

87

(0.83)

21

(1.4)

35

(2.3)

59

(2.0)

50

(1.2)

28

(2.7)

69

(3.4H x 2.7W x 2.7D)

87H x 69W x 69D

1794-ASB/E

1794-ASB2/D

(inches)

millimeters

(3.4)

87

A

B

C

A = Mounting hole dimensions for optional mounting kit

B = DIN rail
C = Secure DIN rail approximately every 200 mm