4 FLEX I/O Remote I/O Adapter Modules

Publication 1794-IN098E-EN-P - January 2011

I/O Rack Number Switch Settings

Primary Chassis

8, 16
and/or
32-point
modules

OFF

OFF

OFF

OFF

OFF

Complementary
Chassis

OFF

OFF

ON

OFF

OFF

1 In Standard – 32 mode, any module in the chassis occupies 32 input points and 32 output

points in the input/output data table.

2 In Complementary – 32 mode, any module in the chassis occupies 32 input points or 32

output points in the input/output data table. If using 8 or 16-point modules,unused points in

the data table are zeroed out.

First I/O Group

1) (see Important)

I/O Rack Number

S1-8

S1-7

I/O Group

S1-6…S1-1

ON

ON

0 (1st)

Refer to addressing mode
tables.

OFF

ON

2 (2nd)

ON

OFF

4 (3rd)

OFF

OFF

6 (4th)

IMPORTANT

1)

In 32-point mode, starting quarter must be 0 (S1-8 and S1-7 on).

S2-8

Mode Switch 0

Refer to mode selection switches, above.

S2-7

Hold Inputs

S2-6

Rack Fault Select

ON

Hold inputs

ON

Disabled (default)

OFF

Reset inputs

OFF

Enabled

S2-5

Mode Switch 1

Refer to mode selection switches, above.

Communication Rate

(32-point Mode Select)

Processor Restart
Lockout

Hold Last State

S2-4

S2-3

Bits/s

S2-2

S2-1

ON

ON

57.6k

ON

Restart

ON

Reset Outputs

OFF

ON

115.2k

OFF

Locked out

OFF

Hold Last State

ON

OFF

230.4k

OFF

OFF

Auto Baud

Use only with 32-point modules.

1)

These switches used to put the adapter in 32-point mode
and perform autobaud.

1)

Cycle power to the adapter or push the RESET button when the baud rate is changed in the

scanner.

32-point Mode Switch Settings

When using
this
addressing
mode

And

Mode

Switch 0

S2-8

Mode

Switch 1

S2-5

Mode

Switch 2

S1-1

Mode

Switch 3

S2-3

Mode

Switch 4

S2-4

8
7
6
5
4
3
2
1

8
7
6
5
4
3
2
1

First I/O

Group

I/O Rack

Number

Mode Switch 2

Mode Switch 1

Hold Inputs
Rack Fault Select

Mode Switch 0

Communication Rate/Mode 3 and 4

Processor Restart Lockout
Hold Last State

S1

S2

on

on

Mode Switch 3

Mode Switch 4

Rack Number

S1 Switch Position

1747-SN

PLC-5

PLC-5/25

PLC-3

6

5

4

3

2

1

Rack 0

Not Valid

Rack 0

Rack 0

ON

ON

ON

ON

ON

ON

Rack 1

Rack 1

Rack 1

Rack 1

OFF

ON

ON

ON

ON

ON

Rack 2

Rack 2

Rack 2

Rack 2

ON

OFF

ON

ON

ON

ON

Rack 3

Rack 3

Rack 3

Rack 3

OFF

OFF

ON

ON

ON

ON

Rack 4

Rack 4

Rack 4

ON

ON

OFF

ON

ON

ON

Rack 5

Rack 5

Rack 5

OFF

ON

OFF

ON

ON

ON

Rack 6

Rack 6

Rack 6

ON

OFF

OFF

ON

ON

ON

Rack 7

Rack 7

Rack 7

OFF

OFF

OFF

ON

ON

ON

Rack 10

Rack 10

Rack 10

ON

ON

ON

OFF

ON

ON

Rack 11

Rack 11

Rack 11

OFF

ON

ON

OFF

ON

ON

Rack 12

Rack 12

Rack 12

ON

OFF

ON

OFF

ON

ON

Rack 13

Rack 13

Rack 13

OFF

OFF

ON

OFF

ON

ON

Rack 14

Rack 14

Rack 14

ON

ON

OFF

OFF

ON

ON

Rack 15

Rack 15

Rack 15

OFF

ON

OFF

OFF

ON

ON

Rack 16

Rack 16

Rack 16

ON

OFF

OFF

OFF

ON

ON

Rack 17

Rack 17

Rack 17

OFF

OFF

OFF

OFF

ON

ON

Rack 20

Rack 20

Rack 20

ON

ON

ON

ON

OFF

ON

Rack 21

Rack 21

Rack 21

OFF

ON

ON

ON

OFF

ON

Rack 22

Rack 22

Rack 22

ON

OFF

ON

ON

OFF

ON

Rack 23

Rack 23

Rack 23

OFF

OFF

ON

ON

OFF

ON

Rack 24

Rack 24

Rack 24

ON

ON

OFF

ON

OFF

ON

Rack 25

Rack 25

Rack 25

OFF

ON

OFF

ON

OFF

ON

Rack 26

Rack 26

Rack 26

ON

OFF

OFF

ON

OFF

ON

Rack 27

Rack 27

Rack 27

OFF

OFF

OFF

ON

OFF

ON

Rack 30

Rack 30

ON

ON

ON

OFF

OFF

ON

Rack 31

Rack 31

OFF

ON

ON

OFF

OFF

ON

Rack 32

Rack 32

ON

OFF

ON

OFF

OFF

ON

Rack 33

Rack 33

OFF

OFF

ON

OFF

OFF

ON

Rack 34

Rack 34

ON

ON

OFF

OFF

OFF

ON

Rack 35

Rack 35

OFF

ON

OFF

OFF

OFF

ON

Rack 36

Rack 36

ON

OFF

OFF

OFF

OFF

ON

Rack 37

Rack 37

OFF

OFF

OFF

OFF

OFF

ON

See note 1 - Rack addresses

Rack 40

ON

ON

ON

ON

ON

OFF

Rack 41

OFF

ON

ON

ON

ON

OFF

Rack 42

ON

OFF

ON

ON

ON

OFF

Rack 43

OFF

OFF

ON

ON

ON

OFF

Rack 44

ON

ON

OFF

ON

ON

OFF

Rack 45

OFF

ON

OFF

ON

ON

OFF

Rack 46

ON

OFF

OFF

ON

ON

OFF

Rack 47

OFF

OFF

OFF

ON

ON

OFF

Rack 50

ON

ON

ON

OFF

ON

OFF

Rack 51

OFF

ON

ON

OFF

ON

OFF

Rack 52

ON

OFF

ON

OFF

ON

OFF

40…76 are available only in

Standard Mode

Rack 53

OFF

OFF

ON

OFF

ON

OFF

Rack 54

ON

ON

OFF

OFF

ON

OFF

Rack 55

OFF

ON

OFF

OFF

ON

OFF

Rack 56

ON

OFF

OFF

OFF

ON

OFF

Rack 57

OFF

OFF

OFF

OFF

ON

OFF

Rack 60

ON

ON

ON

ON

OFF

OFF

Rack 61

OFF

ON

ON

ON

OFF

OFF

Rack 62

ON

OFF

ON

ON

OFF

OFF

Rack 63

OFF

OFF

ON

ON

OFF

OFF

Rack 64

ON

ON

OFF

ON

OFF

OFF

Rack 65

OFF

ON

OFF

ON

OFF

OFF

Rack 66

ON

OFF

OFF

ON

OFF

OFF

Rack 67

OFF

OFF

OFF

ON

OFF

OFF

Rack 70

ON

ON

ON

OFF

OFF

OFF

Rack 71

OFF

ON

ON

OFF

OFF

OFF

Rack 72

ON

OFF

ON

OFF

OFF

OFF

Rack 73

OFF

OFF

ON

OFF

OFF

OFF

Rack 74

ON

ON

OFF

OFF

OFF

OFF

Rack 75

OFF

ON

OFF

OFF

OFF

OFF

Rack 76

ON

OFF

OFF

OFF

OFF

OFF

Not Valid OFF

OFF

OFF

OFF

OFF

OFF

Rack address 77 is an illegal configuration.
PLC-5/11 processors can scan rack 03.
PLC-5/15 and PLC-5/20 processors can scan racks 01…03.
PLC-5/25 and PLC-5/30 processors can scan racks 01…07.
PLC-5/40 and PLC-5/40L processors can scan racks 01…17.
PLC-5/60 and PLC-5/60L processors can scan racks 01…27.
PLC-5/80 processors can scan racks 01…27.
PLC-5/250 processors can scan racks 00…37.
Note 1 – Rack switch 1-1 is used to set a mode in this adapter. As a result, rack addresses
from 40…76 are only available in Standard mode.