Publication 1794-IN124A-EN-P - January 2009

1794-TB3 and -TB3S Terminal Base Wiring for the 1794-IB10XOB6XT

2 and 3-Wire Input Wiring for 1794-IB16XT, -IB10XOB6XT

Configuring Your Module

You configure your output/input module by setting bits in the
configuration word.

Configuration

Setting the Input Filter Time (1794-IB16XT, -IB10XOB6XT)

To set the input filter time, set the associated bits in the output image table
(complementary word) for the module .

As an example for 1794-IB16XT, to increase the off-to-on filter time to 4 ms
for all inputs at address rack 1, module group 0, set bits and program as
shown below .

For 1794-IB10XOB6XT, increase the off-to-on filter time to 8 ms for all
inputs at address rack 1, module group 0, in configuration word 3, by
setting bits as shown below.

Refer to the Input Filter time chart below for other bit settings.

Input Filter Time (1794-IB16XT)

Input Filter Time (1794-IB10XOB6XT)

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

1794-OB8EPXT

Read F7

F6

F5

F4

F3

F2

F1

F0

Reserved (see note)

Write Not

used

FR

O7

O6

O5

O4

O3

O2

O1 O0

Write

1794-OB16PXT

Read Not

used

Write O15 O14 O13 O12 O11 O10 O9

O8

O7

O6

O5

O4

O3

O2

O1 O0

Write
1794-OB
32P only

O
31

O
30

O
29

O
28

O
27

O
26

O
25

O
24

O
23

O
22

O
21

O
20

O
19

O
18

O
17

O
16

1794-IB16XT

Read 1

I15

I14

I13

I12

I11

I10

I9

I8

I7

I6

I5

I4

I3

I2

I1

I0

Read 2

C = Counter Input value of input 15

Write 1 Not used CF

CR

Not used

Input Filter
12-15

Input Filter
0-11

1794-IB10XOB6XT

Read 1 Not used

I9

I8

I7

I6

I5

I4

I3

I2

I1 I0

Write 2 Not used

O5 O4 O3 O2 O1 0O

Write 3 Not used

FT

Not used

Where: O = Output - O0 corresponds to output 0, O1 corresponds to output 1

F = Overload fault bits - 1 = fault present; 0 = no fault

FR = Fault reset bit - 1 = reset output; 0 = no change

I = Input

C = Counter value for input 15

CR = Counter reset

CF = Counter fast - where 1 = fast input (raw data), 0 = standard input filtered data

FT = Input Filter Time for input channels

1794-OB16PXT uses outputs 0-3

NOTE: C, CR and CF not available when used with any series 1794-ASB or 1794-ASB2 remote I/O
adapter modules.
NOTE: The unused lower byte in read word 1 floats during operation. Do not use this byte for fault
status.

See Programming below.

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Inputs

Commons

(1794-TB3 shown)

-V (Supply Common) = Terminals B-16 and B-33
+V (Supply +Voltage In) = Terminals C-34 and C-51

-V

Voltage
In +V

Voltage
Out +V

Voltage

A

B

C

(Use B-33 and C-51 for daisy-chaining to next terminal base unit)

Common

-V

Common

Outputs

= Sink input

= Common

= +V dc

0-15

16-33

34-51

A

B

C

A

B

C

2-Wire Device

(Sourcing Output)

3-Wire Device

(Sourcing Output)

Bits

Description - Filter Time

Filter Time

02

01

00

Inputs 0 thru 11

1794-IB16XT

05

04

03

Inputs 12 thru 15

0

0

0

Filter time 0 (default)

0.25 ms

0

0

1

Filter time 1

0.5 ms

0

1

0

Filter time 2

1 ms

0

1

1

Filter time 3

2 ms

1

0

0

Filter time 4

4 ms

1

0

1

Filter time 5

8 ms

1

1

0

Filter time 6

16 ms

1

1

1

Filter time 7

32 ms

Bits

Description

10

09

08

Filter Time for Inputs

Off to On/On to Off

0

0

0

Filter Time 0

0.25 ms

0

0

1

Filter Time 1

0.5 ms

0

1

0

Filter Time 2

1.0 ms

0

1

1

Filter Time 3

2.0 ms

1

0

0

Filter Time 4

4.0 ms

1

0

1

Filter Time 5

8.0 ms

1

1

0

Filter Time 6

16.0 ms

1

1

1

Filter Time 7

32.0 ms

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Dec.

O:010

FT = 12-15

1794-IB16XT

FT = 0-11

44706

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Dec.

O:010

1794-IB10XOB16XT

FT = 0-9

44708

Fill File
Source
Destination #0:010
Length 1

FLL

1794-IB16XT

I:000

Write filter time on system startup.

Write FT on
complement of
input module.

= 44 Octal or
36

Decimal

00

7

6

5

4

3

2

1

0

1

0

0

1

0

0

44707

Fill File
Source
Destination #0:010
Length 1

FLL

1794-IB10XOB16XT

I:000

Write filter time on system startup.

Write FT on
complement of
input module.

= 5 Octal or
5

Decimal

00

12

11

10

9

8

7

6

5

1

0

1

44709