General specifications – Rockwell Automation 1794-OB8EPXT, 1794-IB16XT, 1794-OB16PXT, 1794-IB10XOB6XT FLEX XT I/O Digital DC Input/Output Modules User Manual

Page 6

Advertising
background image

Publication 1794-IN124A-EN-P - January 2009

6

PN-38723

Copyright © 2009 Rockwell Automation, Inc. All rights reserved.

General Specifications

Environmental

Attribute

Value

Terminal base screw
torque

Determined by installed terminal base

Input filter time

Refer to Input Filter Time setting tables.

Wire size

Determined by installed terminal base

Wiring Category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1.

2 - on signal ports

Dimensions (with module
installed)

94H x 94W x 69D mm

3.7H x 3.7W x 2.7D in.

Enclosure type rating

None (open-style)

Keyswitch position

2

Pilot Duty Rating

2A (-OB16PXT, -IB10XOB6XT, -OB8EPXT)

North American temp
code

T4A

T4 (-OB8EPXT, -IB10XOB6XT)

IEC temp code

T4

Attribute

Value

Operating
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 …70 °C (-4…158 °F)

Storage
temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

–40 to 85 °C (–40 to 185 °F)

Relative
humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10-500 Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):

Operating 30 g

Non-operating 50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2kV at 5kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications (when product is marked)

(1)

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (II 3 G Ex nA IIC T4
X)
EN 60079-0; General Requirements (Zone 2)

TÜV

TÜV Certified for Functional Safety:
up to and including SIL 2

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other

certification details.

Certifications (when product is marked)

(1)

Advertising