5

Publication 1794-IN124A-EN-P - January 2009

Programming the 1794-OB8EPXT

If your program automatically checks for fault bits, bits 8…15 of read word
1 must be masked. This is a sample program for a module at rack address
1, group 0. Add similiar rungs to your program.

Resetting a Fault on the 1794-OB8EPXT

Faults can be reset 3 ways: press the fault reset button on the front of the
module; or toggle the output reset bit (write word 1, bit 08); or cycle
backplane power.

Using the Reset Button on the 1794-OB8EPXT

When you press the reset button, the fault indicator for the faulted output
turns off for about 1.2 s. After the delay, the faulted output attempts to turn
on. If the external condition causing the fault is corrected, the output will
remain on, the fault indicator is off, and the status indicator is on.

Specifications

Output Modules

Input Modules

Attribute

1794-OB8EPXT

1794-OB16PXT

1794-IB10XOB6XT

Number of outputs

8 (1 group of 8),
nonisolated, sourcing

16 nonisolated,
sourcing

6 nonisolated, sourcing

Module location

Cat. No. 1794-TB2, -TB3,
-TB3S, -TBN

Cat. No. 1794-TB2, -TB3, -TB3S

On-state current

1.0 mA min. per channel

2.0 A max. per channel

1.0 mA min. per
channel

500 mA max. per
channel

2.0 mA min.

8.0 mA nom. at 24V DC

11.0 mA max.

On-state voltage
range

19.2 V DC min)

24 V DC nom.

31.2 V DC max.

10 V DC min.

24 V DC nom.

31.2 V DC max.

10 V DC min.

24 V DC nom.

31.2 V DC max.

Supply voltage

24V DC nom.

Voltage range

19.2V DC to 31.2V DC

10V DC to 31.2V DC

10 to 31.2 V DC (includes
5% AC ripple)

Supply current

55mA @ 24V DC

35 mA @ 24V DC

15 mA @ 19.2 V DC

19 mA @ 24 V DC

8 mA @ 10V DC

25 mA @ 31.2V DC

Output current
rating

Max. 2.0 A per output,
10.0 A max. per module
(for example, 8 outputs
@ 1.25 A, 5 outputs @
2.0 A, or similar
combinations totaling
10.0 A or less)

8.0 A (16 outputs @
0.5A)

2.0 A per output

10.0 A max. per module

Surge current

4.0 A for 10 ms,
repeatable every 3 s

1.5 A for 50 ms,
repeatable every 2 s

4.0 A for 50 ms,
repeatable every 2 s

Off-state leakage

0.5 mA max.

On-state voltage
drop

0.2 V DC max.

0.5 V DC max.

1.0 V DC @2 A,

0.5 V DC@1 A max.

Isolation voltage

50V (continuous), Basic
Insulation Type

No isolation between
individual channels

Type tested at 1500V AC
for 60 s, between field
side and system

50V (continuous), Basic
Insulation Type

No isolation between
individual channels

Type tested at 2550V
DC for 60 s, between
field side and system

50V (continuous), Basic
Insulation Type

No isolation between
individual channels

Type tested at 1365V AC
for 60 s, between field
side and system

Output signal delay

Off to On - 0.5 ms max.

On to Off - 1.0 ms max.

Flexbus current

80 mA

60 mA

35 mA

Power dissipation

5 W maximum @ 31.2 V
DC

5.0 W maximum @
31.2 V DC

6.0 W maximum @ 31.2
V DC

MVM

CMP

Source
Mask
Destination

MASKED MOVE

Compare

Expression

N9: < > 0

I:010
FF00
N9:0

O:000

( Out )

This rung turns on output if a fault occurs.

This rung masked bits 8 thru 15.

Thermal dissipation

Max. 17.1 BTU/hr @
31.2 V DC

Max. 17.0 BTU/hr @
31.2 V DC

Max. 20.3 BTU/hr @
31.2 V DC

Indicators (field side
indication, logic
driven)

8 yellow status
indicators

8 red fault indicators

16 yellow status
indicators

6 yellow status
indicators

Fusing

Outputs are
electronically fused

Outputs are
electronically
protected

Module outputs are not

fused.

(1)

(1)

Fusing is recommended. If fusing is desired, you must supply external fusing. Use SAN-O MQ4-3A or Litteolfuse
235-003 fuses.

Attribute

1794-IB10XOB6XT

1794-IB16XT

Number of inputs

10, nonisolated, sinking

16 (1 group of 16), nonisolated,
sinking

Module location

Cat. No. 1794-TB2, -TB3, -TB3S

Cat. No. 1794-TB3, -TB3S Terminal
Base Unit

On-state current

2.0 mA min.

8.0 mA nom. at 24V DC

11.0 mA max.

2.0 mA min.

3.0 mA nom. at 24V DC

5.0 mA max.

On-state voltage
range

10 V DC min.

24 V DC nom.

31.2 V DC max.

Supply voltage

24V DC nom.

24V DC nom,

Voltage range

10 to 31.2 V DC (includes 5% AC
ripple)

10V DC to 31.2V DC

Supply current

15 mA @ 19.2 V DC

19 mA @ 24 V DC

8 mA @ 10V DC

25 mA @ 31.2V DC

4 mA @ 24V DC

Off-state voltage

5.0 V DC max.

Off-state current

1.5 mA min.

Input impedance

4.8 K

Ω

Isolation voltage

50V (continuous), Basic Insulation
Type

No isolation between individual
channels

Type tested at 1365V AC for 60 s,
between field side and system

50V (continuous), Basic Insulation
Type

No isolation between individual
channels

Type tested at 850V AC for 60 s,
between field side and system

Flexbus current

35 mA

30 mA

Power
dissipation

6.0 W maximum @ 31.2 V DC

2 W max. @ 31.2V DC

Thermal
dissipation

Max. 20.3 BTU/hr @ 31.2 V DC

Max 9.2 BTU/hr @ 31.2V DC

Indicators

10 yellow status indicators

(Logix side indication, Logic driven)

16 yellow status indicators

(field side indication, logic driven)