Connect the module to the network by using a tap – Rockwell Automation 1756-CN2_CN2R, Series B ControlLogix ControlNet Interface Module User Manual

Page 15

Advertising
background image

ControlLogix ControlNet Interface Module 15

Publication

1756-IN607A-EN-P - February 2008

Connect the Module to the Network by Using a Tap

To connect the module to the network with a tap, perform this
procedure.

1. Remove and save the dust caps from the ControlNet taps.

Do not allow any metal portions of the tap to contact any conductive
material. If you disconnect the tap from the module, place the dust
cap back on the straight or right-angle connector to prevent the
connector from accidentally contacting a metallic grounded surface.

Segment 1

Segment 2

Dust Cap

Dust Cap

1756-CN2 - Segment 1
1756-CN2R - Segments
1 and 2

2. Connect the tap’s straight or right-angle connector to the

module’s BNC connector.

If your node supports

Then connect the tap’s connector

Non-redundant media

(1756-CN2 module)

To the channel A connector on the module

Channel B on the 1756-CN2R module is not used for
non-redundant media

Redundant media

ATTENTION

From trunkline A to channel A on the 1756-CN2R module

From trunkline B to channel B on the 1756-CN2R module