ControlLogix ControlNet Interface Module 17

Publication

1756-IN607A-EN-P - February 2008

Use this flowchart as a guide.

Turn the chassis
power supply on.

Module status
indicator red?

See Status Indicators
on page 22.

Module performs a
self-test
initialization.

No

Yes

TEST

No

Yes

Module status
indicator red?

Self-test has failed, and
the module displays an
error message. See
pages 23...29.

Replace the
module.

Self-test is complete.
The status indicator
flashes green.

Channel A and B
status indicators
alternately flash.

Channel A and B status
indicators display the
network condition as
listed on page 29.

Module status
displays OK?

No

See the troubleshooting
table on page 23.

Yes

Module is functional
and operating.

OK

A#xx