North American Hazardous Location Approval

The following modules are North American Hazardous Location approved:
1794-APBDPV1.

FLEX I/O PROFIBUS Adapter 1794-APBDPV1

Install Your Adapter Module

Mounting on a DIN rail before installing the Terminal Base Units

1. Position the adapter module (A) on a 35 x 7.5 mm (3 x 0.3 in.) DIN rail (B)

at a slight angle.

2. Hook the lip on the rear of the adapter onto the top of the DIN rail, and

rotate the adapter module onto the rail.

3. Press the adapter module down onto the DIN rail until flush. Locking tab

C will snap into position and lock the adapter module to the DIN rail.

4. If the adapter module does not lock in place, use a screwdriver or similar

device to move the locking tab down while pressing the adapter module
flush onto the DIN rail, and release the locking tab to lock the adapter
module in place. If necessary, push up on the locking tab to lock.

5. Connect the adapter wiring as shown under "Connect Wiring for your

Module".

Remove the debris wrapper before applying power to the module.

Panel/Wall Mounting

If mounting this adapter to a panel or wall, refer to publication

1794-5.13

, “Panel

Mounting Kit, Cat. No. 1794-NM1.”

The following information applies
when operating this equipment in
hazardous locations:

Informations sur l’utilisation de cet
équipement en environnements dangereux :

Products marked “CL I, DIV 2, GP A, B, C, D”
are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining
products within a system, the most adverse
temperature code (lowest “T” number) may
be used to help determine the overall
temperature code of the system.
Combinations of equipment in your system
are subject to investigation by the local
Authority Having Jurisdiction at the time of
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D"
ne conviennent qu’à une utilisation en
environnements de Classe I Division 2 Groupes
A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa
plaque d’identification qui indiquent le code de
température pour les environnements
dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de
température le plus défavorable (code de
température le plus faible) peut être utilisé pour
déterminer le code de température global du
système. Les combinaisons d’équipements dans
le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l’installation.

WARNING

EXPLOSION HAZARD

Do not disconnect equipment unless

power has been removed or the area
is known to be nonhazardous.

Do not disconnect connections to

this equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this
equipment by using screws, sliding
latches, threaded connectors, or other
means provided with this product.

Substitution of components may

impair suitability for Class I,

Division 2.

If this product contains batteries,

they must only be changed in an area
known to be nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION

Couper le courant ou s’assurer que

l’environnement est classé non dangereux
avant de débrancher l'équipement.

Couper le courant ou s'assurer que

l’environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.

La substitution de composants peut

rendre cet équipement inadapté à une
utilisation en environnement de Classe I,
Division 2.

S’assurer que l’environnement est

classé non dangereux avant de changer
les piles.

WARNING

If you insert or remove the module while backplane power is on, an
electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), this equipment must
be powered from a source compliant with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION

To comply with UL restrictions, this equipment must be powered from a
source compliant with the following:

Class 2 or Limited Voltage/Current.

Description

Description

1

Flexbus connector

4

Node address thumbwheel switches

2

24V common connections

5

PROFIBUS connector

3

24V DC connections

6

Status indicators

ATTENTION

During mounting of all devices, be sure that all debris (such as metal chips
and wire stands) is kept from falling into the module. Debris that falls into
the module could cause damage on power up.

WARNING

For Class I Division 2 applications, use only Class I Division 2 listed or
recognized accessories and modules approved for use within the 1794
platform.