Mounting Dimensions

Specifications - Flex I/O PROFIBUS 1794-APBDPV1

Environmental Specifications

Certifications

Specification

Description

I/O capacity

8 modules

Input voltage rating

24V DC nom

19.2V...31.2 V DC (includes 5% AC ripple)

Input current

385 mA max, 309 mA at 24V DC

Inrush current

23 A for 2 ms

Communication rate

All rates up to 12.0 Mbits/s

Indicators

Status- red/green

PROFIBUS- red/green

Flexbus output current

640 mA max

Isolation voltage

50V (continuous), Basic Insulation Type

Profibus to FLEX backplane to power

Routine tested at 850V DC for 1 s, Profibus to Backplane to Power

Type tested at 850V AC for 60 s, Profibus to Backplane to Power

Power dissipation

4.2 W max @ 19.2V DC

Thermal dissipation

Max 14 BTU/hr @ 19.2V DC

Dimensions, approx.

(HxWxD)

87 x 69 x 69 mm

(3.4 x 2.7 x 2.7 in.)

Wire size

- Power

0.34... 2.5 mm

2

(22...12 AWG) solid or stranded copper wire rated at 75 °C

(167 °F ) or greater 1.2 mm (3/64 in.) insulation max

Wire category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

1 on power ports

2 on communications ports

North American temp code

T4

IEC temp code

T4

PROFIBUS cable

Standard drop cable

PROFIBUS connector plug

9-pin D-shell

Emclosure type rating

None (open-style)

(Inches)

Millimeters

(3.4)

87

(3.2)

80

(2.7)

68

(0.83)

21

(1.4)

35

A

(2.3)

59

B

(2.0)

50

(1.2)

28

C

44562

A = Mounting hole dimensions for optional mounting kit
B = DIN rail
C = Secure DIN rail approximately every 200mm (7.87 in.)

Module

1794-APBDPV1

Operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F)

Storage temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

–40…85 °C (–40…185 °F)

Surrounding air temperature, max.

55 °C (131 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):

Operating 30 g

Nonoperating 50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2500 MHz

3V/m with 1 kHz sine-wave 80% AM from 2500…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5:

±2 kV line-earth (CM) on communications ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 10 kHz…80 MHz

Certifications

(when product is marked)

(1)

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates, and other certification

details.

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

See UL File E65584

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA II T4 X