Node address, Gsd requirements, Indicators – Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Communications Adapter User Manual

Page 4

Advertising
background image

4 FLEX I/O PROFIBUS Communications Adapter

Publication 1794-IN114C-EN-P - August 2010

7. Connections G and F are used to pass +V DC power (G) and -V common

(F) to the next module in the series (if required).

Node Address

Set the node address using the thumbwheel switches on the front of the adapter.
Valid settings range from 00...99. Use the + or - buttons to set the node address.
Set the thumbwheel switches to 00 to allow node addressing by software
configuration tool to set the range from 1 to 125. Address changes take effect only
after cycling power.

GSD Requirements

Current functionality of PROFIBUS adapters requires GSD files. These files are
easy to install and are available online at:

www.ab.com/networks/gsd

.

If you want to use a FLEX I/O module not in your GSD file:

1. Go to the GSD website and locate files for the 1794-APBDPV1.

There are two GSD files: One is a standard GSD file with the latest
modules added. The other is a teaching GSD file that teaches your adapter
information required to use the new modules.

2. Load the teaching GSD file into your configuration tool.

This GSD file uses Full format mode.

3. From the list of modules, select the 1794-APBDPV1, then select the first

module that you want to teach.

Add this module in every position after the 1794-APBDPV1.

4. Put the configuration tool in online mode.

The PROFIBUS indicator on the adapter should be solid green and the
Status indicator should be flashing red.

Repeat steps 1…4 for each module that you want to teach.

5. When you have completed the teaching, delete the teaching GSD file from

your configuration tool and load the standard GSD file.

You can now configure the modules as you would your other FLEX I/O
modules.

Indicators

ATTENTION

When connecting wiring, torque terminal screws D, E, F, and G to 0.8 Nm
(7 lb-in).

ATTENTION

Do not wire more than two conductors on any single terminal.

9 9

44560

Thumbwheel switches
for setting the node
address

Status Indicators

Indication

Status

Off

No power

Solid green

Normal operation

Flashing red/OFF

Recoverable fault

- FLEX I/O module defective

- Incorrect module installed

- Node address changed since powerup

Solid red

Unrecoverable fault

- Major hardware failure

PROFIBUS Indicators

Indication

Status

Off

No power or no communication

Solid green

Data is being transmitted and received

Flashing red/OFF

Recoverable fault

- Invalid Send parameter data

- Invalid Check Configuration data

Solid red

Unrecoverable fault

- Unable to communicate

9 9

44561

STATUS Indicator

(green/red)

PROFIBUS Indicator

(green/red)