Configuring and installing your module chapter 3 – Rockwell Automation 1771-DE Absolute Encoder Module User Manual User Manual
Page 19

Configuring and Installing Your Module
Chapter 3
3Ć7
Output Power Supply
To power the eight outputs (Figure 3.5), connect at least one +5 to +24V
DC supply to terminal 1 and terminal 6 (or 7) of the right wiring arm.
You can connect another +5 to +24V DC power supply between terminals
9 and 14 (or 15) of the right wiring arm if, for example, you need two
different load supply voltages.
If you need only one supply voltage, connect a wire between terminals 1
and 9 and connect another wire between terminal 6 (or 7) and terminal 14
(or 15).
Figure 3.5
Connection Diagram for Output Devices
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Output Supply (+5 to 24V dc)
Output 0
Output 1
Output 2
Output 3
Output Common (+5 to 24V dc)
Output Common (+5 to 24V dc)
Not Used
Output Supply (+5 to 24V dc)
Output 4
Output 5
Output 6
Output 7
Output Common (+5 to 24V dc)
Output Common (+5 to 24V dc)
Not Used
Bit 10
Bit 10 / Common
Bit 11
Bit 11 / Common
Input Common (+5V dc)
12838
Right
Wiring
Arm
For Outputs
0 - 3
For Outputs
4 - 7
+5 to 24V
DC User
Supply
+
-
+
-
+5 to 24V
DC User
Supply
+
-
+
-
DC Output
Devices
Input circuitry
Tie Wires
Here
(See Applicable
Codes and Laws)