SoftLogix 5800 Controller 11

Rockwell Automation Publication 1789-IN001K-EN-P - December 2012

The RSLinx software module defaults in Slot 0 if not set up for another slot position.

6. From the Slot Number pull-down menu, choose a slot number.
7. Click OK and then click Close.

Troubleshoot the SoftLogix 5800 Controller

The table describes the status of the controller.

IMPORTANT

Even if you remotely program the controller over a ControlNet or Ethernet link, you must
add the virtual-backplane driver via RSLinx software. If you do not, the SoftLogix
application will not be restored when you restart the computer.

Table 1 - Troubleshooting the Controller

Indicator

Status

Description

RUN

Off

The controller is in Program or Test mode.

Green

The controller is in Run mode.

I/O

Off

Either of these is true:
There are no devices in the I/O configuration.
The controller does not contain a project (controller memory is empty).

Green

The controller is communicating with all the devices in its I/O configuration.

Green flashing

One or more devices in the I/O configuration of the controller are not responding.

Red flashing

A virtual chassis error was detected. Contact your Rockwell Automation
representative or local distributor.

FRC

Off

No tags contain force values.
Forces are inactive (disabled).

Flashing

At least one tag contains a force value.
Force values are inactive (disabled).

Green

Forces are active (enabled).
Force values may or may not exist.

RS232

(1)

Off

No COM port was selected.

Green

The selected COM port was successfully assigned to channel 0 on the controller.

Red

There is a COM port conflict or you selected an invalid COM port number.