12 SoftLogix 5800 Controller

Rockwell Automation Publication 1789-IN001K-EN-P - December 2012

BAT

(1)

Off

Normal operation.

Amber flashing

The controller is in Power-up mode.

Red

Persistent storage for the controller has failed.

OK

Red flashing

Recoverable fault.

Red

Nonrecoverable fault.
Do the following to correct:

1. Remove the controller from the virtual chassis and then reinstall the

controller.

2. Download the project.

3. Place the controller in Run mode.

If the problem continues to occur, contact your Rockwell Automation sales
representative or local Allen-Bradley distributor.

Green

The controller is OK.

(1)

Note that these status indicators function slightly different than the same status indicators on a ControlLogix® controller.

Table 1 - Troubleshooting the Controller (continued)