Rockwell Automation 1789-L10_L30_L60 SoftLogix 5800 Controller Installation Instructions User Manual
Page 12
12 SoftLogix 5800 Controller
Rockwell Automation Publication 1789-IN001K-EN-P - December 2012
BAT
(1)
Off
Normal operation.
Amber flashing
The controller is in Power-up mode.
Red
Persistent storage for the controller has failed.
OK
Red flashing
Recoverable fault.
Red
Nonrecoverable fault.
Do the following to correct:
1. Remove the controller from the virtual chassis and then reinstall the
controller.
2. Download the project.
3. Place the controller in Run mode.
If the problem continues to occur, contact your Rockwell Automation sales
representative or local Allen-Bradley distributor.
Green
The controller is OK.
(1)
Note that these status indicators function slightly different than the same status indicators on a ControlLogix® controller.
Table 1 - Troubleshooting the Controller (continued)
Indicator
Status
Description