Rockwell Automation 1786-RPFM ControlNet Modular Repeater Med-distance Fiber Module Installation Instructio User Manual

Installation instructions, Catalog number 1786-rpfm about the module

Advertising
background image

Installation Instructions

ControlNet Modular Repeater
Medium-distance Fiber Module

Catalog Number 1786-RPFM

About the Module

Use the 1786-RPFM module when you need a medium-distance fiber link
between two ControlNet products. Maximum distance is 3000 m (9843 ft). The
fiber link provides ground isolation between nodes and is less susceptible to
noisy environments than copper media.

Topic

Page

Important User Information

2

Environment and Enclosure

3

North American Hazardous Location Approval

4

European Hazardous Location Approval

5

Module Components

6

Mount the Module

6

Select Fiber Cable

10

Connect the Fiber Module

11

Troubleshoot the Module

12

Specifications

13

Additional Resources

17

IMPORTANT

The supported distance depends on the quality of the fiber,
number of splices, and connectors. The total light loss through
the fiber link must be less than 13.3 dB.

Advertising